| This unit is used where the rejection of hot exhaust air in the building
is not applicable. In this way you may use water to remove space heat
and still adhere to a particular facility or code requirement. The Aqua
Cool Unit also ranges from one to five tons in any voltage.
The design
beyond the ConvertibleAire and Arctic Aire features a special dry, double
insulated safety base pan, special pumps and HD compressor. All separate
condensate flows directly to a condensate pump with check valves and quick
connect fittings.
|
 |
| |
|
|
|
|
MODEL
|
OWC1211
|
OWC1811
|
OWC2412
|
OWC3612
|
OWC3632
|
OWC6012
|
OWC6032
|
|
Nominal Cooling Capacity 1
|
13,780
|
18,840
|
23,950
|
36,100
|
36,100
|
60,100
|
60,100
|
|
Voltage
|
115/60/1 or 208/230/60/1
|
208/230/60/1
|
208/230/3
|
208/230/1
|
208/230/3
|
|
Cooling Amps 5
|
10.5/5.3
|
12.0/6.2
|
8.6
|
13.0
|
9.4
|
20.7
|
14.8
|
|
Cooling Watts 5
|
1050
|
1400
|
1990
|
3000
|
3000
|
5350
|
5350
|
|
E.E.R.
|
13.1
|
13.5
|
12.3
|
12.0
|
12.0
|
11.3
|
11.3
|
|
In Rush Current (AMPS)
|
79
|
92.6
|
64.6
|
109.6
|
103.4
|
183.1
|
134.2
|
|
Fuse/Breaker (AMPS)
|
15
|
15
|
20
|
20
|
20
|
30
|
20
|
|
Plug Type
|
5-15P
|
5-15P
|
6-20P
|
6-20P
|
6-30P
|
6-30P
|
L15-20P
|
|
Compressor HP
|
1
|
1 1/2
|
2
|
3
|
3
|
5
|
5
|
|
Compressor RLA
|
9.3
|
11.4
|
8.3
|
17.9
|
11.4
|
28.0
|
20.0
|
|
Compressor LRA
|
58
|
65
|
49
|
88
|
77
|
169
|
123
|
|
Evaporator CFM 2
|
400
|
600
|
810
|
1310
|
1310
|
2200
|
2200
|
|
Evap Motor HP
|
1/15
|
1/5
|
1/3
|
1/2
|
1/2
|
1
|
1
|
|
Evap Motor Watts
|
200
|
210
|
350
|
375
|
375
|
550
|
550
|
|
Condenser Water Flow at 60°F
inlet GPM
|
0.75
|
1.10
|
1.55
|
2.20
|
2.20
|
5.50
|
5.50
|
| at
85°F inlet GPM |
3.0
|
4.5
|
6.0
|
9.0
|
9.0
|
15.0
|
15.0
|
|
Condenser Coil Pressure Drop-PSI
|
.40
|
.40
|
.20
|
.40
|
.40
|
.40
|
.40
|
|
Water Valve Pressure Drop-PSI
|
2.0
|
|
Water Valve Connection 4
|
3/8 MF
|
5/8 MF
|
|
Drain Connection
|
3/8 MF
|
|
Condensate Pump Head (Standard)
|
20 Feet
|
|
Sound Level 3
|
52
|
57
|
60
|
62
|
62
|
69
|
69
|
|
R-22 Charge Oz.
|
19
|
22
|
24
|
36
|
36
|
68
|
|
(A) Height with Casters
|
31 1/2
|
37 1/2
|
47
|
52 1/4
|
|
(D) Height without Casters
|
28 1/2
|
34 1/2
|
42 1/2
|
46 1/2
|
|
(B) Width
|
20 1/8
|
24 1/4
|
28 1/4
|
|
(C) Depth
|
13 1/8
|
13
|
15 1/2
|
39 |
|
Net Weight
|
120
|
165
|
170
|
225
|
225
|
350
|
350
|
|
Shipping Weight
|
125
|
175
|
180
|
235
|
235
|
385
|
385
|
|
Shipping Volume
|
9
|
18
|
18
|
21 |
21
|
36
|
36
|
| |
| Nominal Capacity is net BTU/HR at 80°F DB/67°F WB
return air or 85°F EWT to 95°F LWT (#GPM/Ton). |
| CFM
with free discharge. |
| Sound
Pressure, dB at 5 feet Com. Config. |
| Size
3/8 valve used on model 12, 18, 24 (3/8 MF Fitting) 5/8 valve used
on models 36 & 60 |
| Amps
& Watts at 208 volts |
| • All
units available in 220/50 cycle |
| • Subject to change without notice. Aprill 4, 2000 |